Cold Water Storage
CIBSE/IHVE Plumbing Engineering Services Design Guide method: Storage Required = Daily Demand × Storage % (not peak-flow × hours – UK cisterns are primarily sized to cover a mains interruption, not smooth peak demand). Legionella check is a turnover calc: Selected Tank ÷ Average Hourly Demand, flagged if it exceeds 24 hours.
Result
Hot Water Storage
CIBSE Guide G Section 2 / CIBSE Journal CPD Module 74 method: Daily Demand → Peak Period Demand (editable fraction – not a published standard figure) → Storage Required (grossed up by the 80% usable-storage/stratification factor) → Required Reheat kW to recover the selected volume within the peak period.
Result
Pipe Sizing
CIBSE Guide C Haaland equation (Ch.4, Eq 4.5) for the Darcy friction factor – smallest standard size whose friction pressure drop is at or below your target rate.
Result
Pipe Insulation Condensation Risk
Checks an insulated pipe's outer surface temperature against the dew point of the surrounding air (BS 5422-style, radial/cylindrical resistance network) – CIBSE Guide C Table 3.25 film coefficients.